| Home | Mailing Lists | Bookstore | Weather | Tide Predictions | Bowditch |

T&T: Fw: wire size

From: Dan Hall (no email)
Date: Mon Aug 01 2005 - 01:29:37 EDT

  • Next message: (no name): "T&T: Buffer Polisher"

    This is an interesting table Tom. The cable may well be rated at 105* C.
    Unfortunately no other part of the system will be rated at that temperature.
    So if you terminate this 105* cable in a breaker rated at 75* you will only be
    allowed to use the 75* rating of the wire. If you were to load a #18 wire with
    20 amps I would not be at all surprised if the temperature of the wire would
    soar above 75*C. Such temperatures would quickly break down the internal
    workings of a breaker or fixture.
    This does not mean that the 105* rating is wasted. What it means is that if
    the temperature of the wire is raised to 105* at some spot locally in it's
    routing, perhaps where in close proximity to a heat source, the insulation
    will not break down and cause a short circuit.
    We run into this derating situation in the field all the time. The higher
    temperature wires are of course better for many installations but may not be
    ideal where flexibility or resistance to other stressors may be required.

    For all around use I prefer XHHW-2. This may not be ideal on a boat because it
    gives off some pretty nasty chemicals when burned. There are Teflon
    insulations (spendy) that are required for aircraft use. I dunno if they are
    used on boats.

    Dan
      ----- Original Message -----
      From: Tom Manning
      To: ;
      Sent: Sunday, July 31, 2005 2:13 PM
      Subject: T&T: wire size

    Are you guys saying the Ancor Table below is incorrect? Or, am I assuming
    something different from you guys? 120 volt, 54.167 amp generator are my
    assumptions. Along the same line, what would you recommend for a 120 volt
    only, 42 amp generator? Assuming the generator is 120 volts, it can produce up
    to 55 amps. According to a table I have, you should use #6 wire from the
    generator to the distribution panel. > If the generator is 120/240 Volt, then
    you'll have up to 27 amps in each > leg, so #10 wire is adequate.< WARNING:
    Incorrect and dangerous thinking. This statement would only be true in a
    perfectly balanced system. Never the less, the National Electrical Code and
    good practice would call for #6 in most wire types. TECHNICAL INFORMATION

            Table F: Allowable Amperage of Conductors of 50 Volts or More

            The current values shown in Table F and also on Table D do not
    consider voltage drop for conductors under 50 volts. The values shown on the
    ampacity table are the maximum safe amperages which the conductor can carry on
    a continuous basis. They do not apply to intermittent starting loads such as
    motor start currents. Since all ANCOR Boat Cable is 1050 C insulated, only
    that temperature rating is shown.

            Due to the higher ambient temperatures in engine spaces and the heat
    retention of large wire bundles, a "correction factor" must be used to derate
    the wire by increasing conductor size. Table F takes into consideration these
    factors and should be used to select conductor sizes for circuits over 50
    volts. Note that for electrical systems under 50 volts, voltage drop is the
    controlling factor and the tables on pages 14 and 15 should be used.

                 2 Conductors 1050 C (2210 F)
                 3 Conductors 1050 C (2210 F)
                 4 to 6 Conductors 1050 C (2210 F)
                 7 to 24 Conductors 1050 C (2210 F)

                  Conductor
                 Outside
                 Inside
                 Outside
                 Inside
                 Outside
                 Inside
                 Outside
                 Inside

                  Size
                 Engine
                 Engine
                 Engine
                 Engine

                  (AWG)
                 Space
                 Space
                 Space
                 Space

                  18
                 20
                 17.0
                 14.0
                 11.9
                 12.0
                 10.2
                 10.0
                 8.5

                  16
                 25
                 21.3
                 17.5
                 14.9
                 15.0
                 12.8
                 12.5
                 10.6

                  14
                 35
                 29.8
                 24.5
                 20.8
                 21.0
                 17.9
                 17.5
                 14.9

                  12
                 45
                 38/3
                 31/5
                 26.8
                 27.0
                 23.0
                 22.5
                 19.1

                  10
                 60
                 51.0
                 42.0
                 35.7
                 36.0
                 30.6
                 30.0
                 25.5

                  8
                 80
                 68.0
                 56.0
                 47.6
                 48.0
                 40.8
                 40.0
                 34.0

                  6
                 120
                 102.0
                 84.0
                 71.4
                 72
                 61.2
                 60.0
                 51.0

                  4
                 160
                 136.0
                 112.0
                 95.2
                 96.0
                 81.6
                 80.0
                 68.0

                  3
                 180
                 153.0
                 126.0
                 107.1
                 108.0
                 91.8
                 90.0
                 76.5

                  2
                 210
                 178.5
                 147.0
                 125.0
                 126.0
                 107.1
                 105.0
                 89.3

                  1
                 245
                 208.3
                 171.5
                 145.8
                 147.0
                 125.0
                 122.5
                 104.1

                  1/0
                 285
                 242.3
                 199.5
                 169.6
                 171.0
                 145.4
                 142.5
                 121.1

                  2/0
                 330
                 280.5
                 231.0
                 196.4
                 198.0
                 168.3
                 165.0
                 140.3

                  3/0
                 385
                 327.3
                 269.5
                 229.1
                 231.0
                 196.4
                 192.5
                 163.6

                  4/0
                 445
                 378.3
                 311.5
                 264.8
                 267.0
                 227.0
                 222.5
                 189.1

           Table F is supplied to eliminate the need for calculating the
    corrections for multi-conductor cable bundles to Table E. The values are
    already corrected.
           Number of current
                 Correction

                  carrying conductors:
                 Factor

                  3
                 0.70

                  4 to 6
                 0.60

                  7 to 24
                 0.50

                  25 and above
                 0.40

           a.. Note: These tables only apply for 1050 C (2210 F) wire and other
    premium wire and should not be used for lesser grades of wire and cable.
              b.. Reprinted at the courtesy of the United States Coast Guard
    Electrical System Compliance Guideline.

           *There is NO LIMIT on conductors in a bundle under 50 Volts.

            ANCOR Marine GradeT Products . (800) 424-WIRE . www.ancorproducts.com
    _______________________________________________
    http://lists.samurai.com/mailman/listinfo/trawlers-and-trawlering

    To unsubscribe send email to
     with the word
    UNSUBSCRIBE and nothing else in the subject or body of the message.

    Trawlers & Trawlering and T&T are trademarks of Water World
    Productions. Unauthorized use is prohibited.


  • Next message: (no name): "T&T: Buffer Polisher"



    | Home | Mailing Lists | Bookstore | Weather | Tide Predictions | Bowditch | Trawlerworld |