> I can see paralleling the two shore power circuits together, either
> internally or via
>an adapter, but why if two 30-amp outlets are available on the dock, would
>the builder have provided a means by which to select one or the other 110
>VAC cord, but not both?
>
>Any ideas?
If a "both" position were provided, it would be possible to have one one
wire plugged in at the dock, while another was was not. The male connector
on the one which was not plugged in would then be live and would create a
serious shock hazard.
Best,
Steve
Steve Dubnoff
1966 Willard 47' Dover Pilothouse