    >Had tried to install one in the engine room with the load on one
    > side, and the line output to the strings of outlets in the galley.

    This is backwards. The terminals marked "line" on the GFCI are for the
    incoming line wires. The string of outlets downstream should have been
    connected to the "load" terminals.

    I have the same situation. A GFCI receptacle in the engine room also
    protects the receptacle at the galley and in the aft stateroom.

    Andy

    Andy & Linda Woods
    Grand Folly
    1970 Grand Banks 36 Classic
    Georgetown, MD