Check out the bookstore at IRBS.com
| Home | Mailing Lists | Bookstore | Weather | Tide Predictions | Bowditch |

Re: lv-ab: Re: Worthless Circuitbreakers

From: ahmet erkan (no email)
Date: Mon Sep 01 2003 - 10:57:24 EDT

  • Next message: Lew Hodgett: "Re: lv-ab: Re: Worthless Circuitbreakers"

    I agree with Lew, "This ain't rocket science" however I disagree with every
    other conclusion. (Hoping we could disagree and still remain friendly.)

    IMHO, if we are trying to establish a certain circuit breaker's reliability
    to trip and not damage itself, this has been accomplished. (Occasional
    tripping under overload for a test period of over a decade tells me this CB
    can deal with the stresses it is subjected to in this application.)

    If we are trying to figure out why Norm's CB's trip, the current carying
    capability of the feeder may play a different role for the Windlass vs the
    Inverter. The Inverter typically has a feedback loop that tries to maintain
    constant output voltage when the input voltage sags, therefore the output
    power remains constant. As an example, if the feeder wires to the inverter
    drop 10% of the DC bus voltage, the inverter will require about 10% more
    input current to maintain the output voltage, thus the CB current will
    increase by 10% getting it closer to tripping. (Bottom line : Use heavier
    wires and the same CB may stop tripping.)
    On the other hand the Windlass may not have a feedback loop, thus it's input
    current may decrease when the input voltage decreases, thus causing the
    circuit breaker current to also decrease. (Bottom line : Use heavier wires
    and the same CB may trip even faster)

    The manufacturer of the Inverter needs to specify the maximum current the
    device will cause in the input wires, during all possible operating
    conditions including overload. We the user should use a circuit breaker that
    is rated a little higher than the specified maximum. As an alternative, we
    can install an interlock system that will disable other loads when a certain
    load is turned on, thus prevent the overload from ever taking place.
    The manufacturer of the windlass needs to specify it's locked rotor current
    vs. input voltage and a CB should be used that is rated higher than the
    specified maximum current. If more effort is needed from the Windlass,
    heavier wiring and CB needs to be used.

    IMHO it is an undesirable and potentially unsafe situation to rely on
    mechanical contacts interrupting large currents on a regular basis. The
    manufacturer of the windlass should provide some form of electronic sensing
    and maybe timing of the overload condition and either sounding an alarm or
    overriding the operator controls. (For mission critical equipment such as a
    windlass there should also be an override for the protection circuit that
    can be activated in the heat of a battle.)

    Due to manufacturer's providing us with a lot of BS and inferior products,
    if the frequent CB tripping is to be employed as an economical means of
    protection, IMHO there should be heavy bare wires connected to the CB
    terminals, the other ends should be bolted to large busbars with sufficient
    surface area, serving as heatsinks. The insulated wiring can route the
    current safely from the bussbar to the loads. If the CB contacts have
    carbonized over the years of hard use and one day they decide to begin
    arcing and dissipating large amounts of heat, the fire will be contained in
    a non flammable CB enclosure and the heat will not conduct out of it through
    the wiring. If there is nothing to burn such as wiring insulation the CB
    will eventually melt up enough metal at it's contacts and the circuit will
    open. Hot wires with burning insulation and no means to shut-off the power
    is indeed a nightmare and I would not want any sailor to be subjected to it.

    Have a good Labor day weekend,

    Ahmet

    >From: Lew Hodgett <>
    >To:
    >Subject: lv-ab: Re: Worthless Circuitbreakers
    >Date: Sun, 31 Aug 2003 15:24:28 -0700
    >
    > writes:
    >
    > >Lew,
    > >
    > >I said very clearly in my message:
    > >
    > >Quote
    > >The fact is that both of these breakers have tripped when they should
    > >have,
    > >with no apparent ill effects.  The house buss breaker has tripped
    > >several times
    > >when I have called upon my anchor windlass to maximum effort, and the
    > >breaker
    > >feeding the Trace inverter regularly trips when someone tries to
    > >operate two
    > >high load galley appliances at the same time.  These two breakers have
    > >been in
    > >operation for almost a decade and seem to work just fine.
    > >Unquote
    >
    >The above indicates the following:
    >
    >1) If the feeder supplying the windlass has been properly sized, then the
    >c'bkr tripping represents a nuisance trip which is not within the scope
    >of proper operation.
    >
    >2) If the c'bkr is the proper size to protect the feeder supplying the
    >windlass, then the feeder is undersized for the application.
    >
    >In any event, there is a problem.
    >
    >Similar logic applies to the Trace inverter; however, if the output of
    >the inverter itself is placed in an overload condition, then there is a
    >basic circuit design problem.
    >
    >As the popular saying puts it, "This ain't rocket science".
    >
    >
    >Lew
    >
    >S/A: Challenge (Under Construction in the Southland)
    >
    >There are no problems, only varying degrees of Challenging Opportunity.
    >
    >
    >________________________________________________________________
    >The best thing to hit the internet in years - Juno SpeedBand!
    >Surf the web up to FIVE TIMES FASTER!
    >Only $14.95/ month - visit www.juno.com to sign up today!
    >___________________________________________________________________________
    >|| The Live-Aboard List : send a "subscribe" or "unsubscribe" request ||
    >|| in body of message to: ||

    _________________________________________________________________
    MSN 8: Get 6 months for $9.95/month. http://join.msn.com/?page=dept/dialup

    ___________________________________________________________________________
    || The Live-Aboard List : send a "subscribe" or "unsubscribe" request ||
    || in body of message to: ||


  • Next message: Lew Hodgett: "Re: lv-ab: Re: Worthless Circuitbreakers"



    | Home | Mailing Lists | Bookstore | Weather | Tide Predictions | Bowditch | Trawlerworld |